Product Detail

8.7/15 kV XLPE Insulated, Double Steel Tape Armored, Three Core Cables with Copper Conductor

Code

YXC8VZ4V-R, N2XSEYBY, CU/XLPE/CTS/PVC/STA/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502 - 2, VDE 0276 – 620

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Filler

8. Inner sheath

9. Galvanized double steel tape

10. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

8.7/15 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

57.0

5200

1000

0.524

0.397

0.160

178

173

3x50/16

60.5

5500

500

0.387

0.377

0.175

210

206

3x70/16

64.0

6400

500

0.268

0.356

0.196

256

257

3x95/16

68.5

7600

500

0.193

0.339

0.218

307

313

3x120/16

72.5

8750

500

0.153

0.325

0.240

349

360

3x150/25

75.5

10000

250

0.124

0.315

0.258

392

410

3x185/25

80.0

11600

250

0.0991

0.305

0.280

443

469

3x240/25

88.0

14600

250

0.0754

0.292

0.315

513

553

3x300/25

93.0

17050

250

0.0601

0.284

0.343

576

635

3x400/35

101.0

21000

200

0.0470

0.273

0.385

650

731

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources