Product Detail
0.6/ 1kV XLPE Insulated, Double Steel Tape Armored Multi-Core Cables with Copper Conductor
Code YXZ4V-U, YXZ4V-R, CU/XLPE/DSTA/PVC, N2XBY U: Solid
Conductor R: Stranded Rigid Conductor Standards IEC 60502-1, VDE 0276-603 |
Application Characterized with low
dielectric loss. Used indoor, outdoor or underground; in cable ducts; in
power or switching stations; at local energy distribution networks;
industrial plants where risk of mechanical damage exits. Construction 1. Solid or stranded copper conductors 2. XLPE
insulation 3. Filler 4.
Galvanized double steel tape 5. PVC
outer jacket |
|||||||||
Technical
Data |
|
|
||||||||
Max. operating temperature |
: |
90 oC |
||||||||
Max. short circuit temperature |
: |
250 oC (Max. 5 sec.) |
||||||||
Rated voltage |
: |
0.6 / 1kV |
||||||||
Min. bending radius |
: |
15 x D |
||||||||
(D: Cable outer diameter) |
||||||||||
DIMENSIONS
AND WEIGHTS |
ELECTRICAL
PROPERTIES |
|
||||||||
Nominal |
Overall |
|
|
DC
Conductor |
Current
Carrying Capacity |
|
||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In
Ground at |
In Air
at |
|
|||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|
|||
mm2 |
mm |
kg/km |
m |
Ohm/km |
A |
A |
|
|||
3x1.5 |
13.0 |
300 |
1000 |
12.1 |
30 |
24 |
|
|||
3x2.5 |
13.5 |
350 |
1000 |
7.41 |
40 |
32 |
|
|||
3x4 |
14.5 |
430 |
1000 |
4.61 |
52 |
42 |
|
|||
3x6 |
15.5 |
520 |
1000 |
3.08 |
64 |
53 |
|
|||
3x10 |
18.5 |
730 |
1000 |
1.83 |
86 |
73 |
|
|||
3x16 |
20.5 |
950 |
1000 |
1.15 |
111 |
96 |
|
|||
3x25 |
24.0 |
1400 |
1000 |
0.727 |
143 |
130 |
|
|||
3x35 |
26.0 |
1750 |
1000 |
0.524 |
173 |
160 |
|
|||
3x50 |
29.0 |
2250 |
1000 |
0.387 |
205 |
195 |
|
|||
3x70 |
33.5 |
3100 |
1000 |
0.268 |
252 |
247 |
|
|||
3x95 |
37.5 |
4050 |
1000 |
0.193 |
303 |
305 |
|
|||
3x120 |
42.0 |
5300 |
500 |
0.153 |
346 |
355 |
|
|||
3x150 |
47.0 |
6500 |
500 |
0.124 |
390 |
407 |
|
|||
3x185 |
51.5 |
7900 |
500 |
0.0991 |
441 |
469 |
|
|||
3x240 |
58.0 |
10100 |
250 |
0.0754 |
511 |
551 |
|
|||
3x300 |
65.5 |
12450 |
250 |
0.0601 |
580 |
638 |
|
|||
3x400 |
73.5 |
16100 |
250 |
0.0470 |
663 |
746 |
|
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground : 200C; buried in 70
cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7
In Air : 300C; load
factor 1.0
Number of System : 1
Resources
Get a copy of brochure on Cu Conductor, XLPE Insulated, DST Armored, Multi Core (3) LV Cables.