Product Detail

18/30 kV XLPE Insulated, Flat Steel Wire Armored, Three Core Cables with Copper Conductor

Code

YXC8VZ3V-R, N2XSEYFGY

R: Stranded Rigid Conductor

Standards

IEC 60502 - 2, VDE 0276 – 620; BS 6622

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Filler

8. Inner sheath

9. Galvanized flat steel wire

10. Galvanized steel tape

11. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

18/30 kV

 

 

19/33 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

74.5

7850

500

0.524

0.457

0.114

-

-

3x50/16

78.0

8750

500

0.387

0.434

0.124

214

217

3x70/16

81.5

9950

500

0.268

0.410

0.137

261

269

3x95/16

85.5

11250

250

0.193

0.389

0.150

313

326

3x120/16

89.5

12600

250

0.153

0.372

0.163

356

377

3x150/25

93.0

14000

250

0.124

0.360

0.174

400

426

3x185/25

97.0

15700

250

0.0991

0.348

0.188

441

488

3x240/25

104.0

18500

250

0.0754

0.331

0.209

510

576

3x300/25

109.5

21150

200

0.0601

0.321

0.226

-

-

3x400/35

117.5

25350

200

0.0470

0.307

0.251

-

-

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources