0.6/ 1kV XLPE Insulated, Flat Steel Wire Armored Multi-Core Cables with Copper Conductor

Code

YXZ3V-R, N2XFGY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Stranded copper conductors

2. XLPE insulation

3. Filler

4. Galvanized flat steel wire

5. Galvanized steel binding strap

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

2x25

24.5

1410

1000

0.727

145

155

 

2x35

26.3

1700

1000

0.524

175

195

 

2x50

28.8

2100

1000

0.387

210

235

 

2x70

32.9

2750

1000

0.268

255

300

 

2x95

36.9

3500

1000

0.193

310

370

 

2x120

40.4

4300

500

0.153

355

430

 

2x150

44.3

5150

500

0.124

400

490

 

2x185

49.1

6300

500

0.0991

455

570

 

2x240

54.7

7950

250

0.0754

530

680

 

2x300

59.6

9550

250

0.0601

605

785

 

2X400

67.2

12150

250

0.0470

690

860

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.