Product Detail

0.6/ 1kV XLPE Insulated, Flat Steel Wire Armored Multi-Core Cables with Copper Conductor

Code

YXZ3V-R, N2XFGY

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Stranded copper conductors

2. XLPE insulation

3. Filler

4. Galvanized flat steel wire

5. Galvanized steel binding strap

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

3x25

25.0

1600

1000

0.727

143

130

 

3x35

27.0

1950

1000

0.524

173

160

 

3x50

30.0

2550

1000

0.387

205

195

 

3x70

34.5

3450

1000

0.268

252

247

 

3x95

38.5

4400

1000

0.193

303

305

 

3x120

42.5

5400

500

0.153

346

355

 

3x150

47.0

6600

500

0.124

390

407

 

3x185

51.5

8000

500

0.0991

441

469

 

3x240

58.5

10200

250

0.0754

511

551

 

3x300

65.5

12500

250

0.0601

580

638

 

3x400

74.0

16300

250

0.0470

663

746

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, FSW Armored, Multi Core (3) LV Cables.