Product Detail

40/69 kV XLPE Insulated, Radial and Longitudinally Sealed, Single Core Cables with Copper Conductor

Code

N2XS(FL)2Y, CU/XLPE/LW/CWS/LW/PE

Standards

VDE 0276-632, IEC 60840

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts. In case water sneaks into cable due to any mechanical damage, swellable tape prevents penetration of water inside the cable.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive swelling tape

6. Copper screen

7. Semi-conductive swelling tape

8. PE coated aluminum foil

9. PE outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

40/69 kV

Min. bending radius

:

20 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Operation

Capacitance

(approx.)

DC Conductor

Resistance at

20 0C Max

Current Carrying Capacity (A)

mm2

mm

kg/km

µF/km

Ohm/km

In ground

at 20oC

In duct

at 20oC

In air at 30oC

***

***

1x240/25

61.0

4700

0.180

0.0754

530

483

692

606

1x300/25

63.0

5400

0.190

0.0601

599

544

795

693

1x400/25

66.0

6300

0.210

0.0470

683

616

925

802

1x500/35

70.0

7600

0.230

0.0366

780

729

1075

929

1x630/35

75.0

9000

0.260

0.0283

886

828

1247

1066

1x800/35

79.0

10700

0.280

0.0221

997

929

1432

1210

1x1000/50

84.0

12900

0.310

0.0176

1173

1087

1728

1473

1x1200/50

90.0

15000

0.330

0.0151

1270

1173

1894

1611

1x1600/70

95.0

18800

0.370

0.0113

1465

1375

2245

1883

1x2000/95

102.0

22800

0.410

0.0090

1627

1530

2556

2111

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, HV Cables (40/69 kV).