Product Detail

64/110 kV XLPE Insulated, Radial and Longitudinally Sealed, Single Core Cables with Copper Conductor

Code

N2XS(FL)2Y, CU/XLPE/LW/CWS/LW/PE

Standards

VDE 0276-632, IEC 60840

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts. In case water sneaks into cable due to any mechanical damage, swellable tape prevents penetration of water inside the cable.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive swelling tape

6. Copper screen

7. Semi-conductive swelling tape

8. PE coated aluminum foil

9. PE outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

64/110 kV

Min. bending radius

:

20 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Operation

Capacitance

(approx.)

DC Conductor

Resistance at

20 0C Max

Current Carrying Capacity (A)

mm2

mm

kg/km

µF/km

Ohm/km

In ground

at 20oC

In duct

at 20oC

In air at 30oC

***

***

1x240/25

68.0

5400

0.180

0.0754

528

495

682

605

1x300/25

71.0

6100

0.190

0.0601

597

559

783

692

1x400/35

74.0

7100

0.210

0.0470

681

650

909

800

1x500/35

78.0

8400

0.220

0.0366

775

739

1053

922

1x630/35

82.0

9900

0.240

0.0283

884

841

1226

1065

1x800/35

86.0

11600

0.260

0.0221

994

945

1406

1208

1x1000/50

92.0

14000

0.290

0.0176

1169

1106

1695

1645

1x1200/50

97.0

16000

0.310

0.0151

1264

1231

1849

1595

1x1600/70

104.0

20000

0.340

0.0113

1456

1415

2185

1860

1x2000/95

115.0

24000

0.370

0.0090

1618

1570

2487

2089

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated HV Cables (64/110 kV).