Product Detail
76/132 kV XLPE Insulated, Radial and Longitudinally Sealed, Single Core Cables with Copper Conductor
Code N2XS(FL)2Y,
CU/XLPE/LW/CWS/LW/PE Standards VDE 0276-632, IEC 60840 |
Application Characterized with low
dielectric loss. Used in energy networks where load may change suddenly. Laid
in residential or industrial areas, and underground in ducts. In case water
sneaks into cable due to any mechanical damage, swellable tape prevents
penetration of water inside the cable. Construction 1. Stranded copper conductors 2. Inner
semi-conductive layer 3. XLPE
insulation 4. Outer
semi-conductive layer 5.
Semi-conductive swelling tape 6. Copper
screen 7. Semi-conductive
swelling tape 8. PE coated
aluminum foil 9. PE outer jacket |
||||||||||
Technical
Data |
|
|
|||||||||
Max. operating temperature |
: |
90 oC |
|||||||||
Max. short circuit temperature |
: |
250 oC (Max. 5 sec.) |
|||||||||
Rated voltage |
: |
76/132 kV |
|||||||||
Min. bending radius |
: |
20 x D |
|||||||||
(D: Cable outer diameter) |
|||||||||||
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
||||||||||
Nominal Cross Section |
Overall Diameter (approx.) |
Net Weight (approx.) |
Operation Capacitance (approx.) |
DC
Conductor Resistance
at 20 0C
Max |
Current
Carrying Capacity (A) |
||||||
mm2 |
mm |
kg/km |
µF/km |
Ohm/km |
In
ground at 20oC |
In duct at 20oC |
In
air at 30oC |
||||
*** |
*** |
||||||||||
1x240/25 |
76.0 |
7100 |
0.150 |
0.0754 |
525 |
492 |
673 |
601 |
|||
1x300/25 |
79.0 |
7800 |
0.160 |
0.0601 |
593 |
555 |
774 |
688 |
|||
1x400/35 |
82.0 |
8900 |
0.170 |
0.0470 |
675 |
632 |
896 |
792 |
|||
1x500/35 |
85.0 |
10000 |
0.190 |
0.0366 |
767 |
716 |
1033 |
908 |
|||
1x630/35 |
89.0 |
11500 |
0.210 |
0.0283 |
872 |
811 |
1200 |
1045 |
|||
1x800/35 |
93.0 |
13500 |
0.240 |
0.0221 |
979 |
932 |
1374 |
1182 |
|||
1x1000/50 |
100.0 |
15500 |
0.230 |
0.0176 |
1145 |
1087 |
1649 |
1420 |
|||
1x1200/50 |
105.0 |
17500 |
0.230 |
0.0151 |
1233 |
1212 |
1801 |
1539 |
|||
1x1600/70 |
112.0 |
21500 |
0.250 |
0.0113 |
1414 |
1388 |
2125 |
1784 |
|||
1x2000/95 |
120.0 |
25800 |
0.310 |
0.0090 |
1569 |
1532 |
2418 |
2003 |
|||
|
|
|
|
|
|
|
|
|
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground :
200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load
factor 0.7
In Air :
300C; load factor 1.0
*** :
Flat formation; clearance between cables in air = 1 x cable outer diameter; in
ground = 7cm
*** :
Trefoil formation
Number of System : 1
Resources
Get a copy of brochure on Cu Conductor, XLPE Insulated HV Cables (76/132 kV).