Product Detail

89/154 kV XLPE Insulated, Radial and Longitudinally Sealed, Single Core Cables with Copper Conductor

Code

N2XS(FL)2Y, CU/XLPE/LW/CWS/LW/PE

Standards

VDE 0276-632, IEC 60840

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts. In case water sneaks into cable due to any mechanical damage, swellable tape prevents penetration of water inside the cable.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive swelling tape

6. Copper screen

7. Semi-conductive swelling tape

8. PE coated aluminum foil

9. PE outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

89/154 kV

Min. bending radius

:

20 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Operation

Capacitance

(approx.)

DC Conductor

Resistance at

20 0C Max

Current Carrying Capacity (A)

mm2

mm

kg/km

µF/km

Ohm/km

In ground

at 20oC

In duct

at 20oC

In air at 30oC

***

***

1x300/25

85.0

7100

0.150

0.0601

591

553

765

684

1x400/35

89.0

8200

0.160

0.0470

673

629

887

789

1x500/35

93.0

9700

0.180

0.0366

766

713

1027

907

1x630/35

96.0

11400

0.190

0.0283

871

829

1193

1043

1x800/35

102.0

13600

0.200

0.0221

977

928

1367

1181

1x1000/50

106.0

16000

0.210

0.0176

1143

1081

1639

1415

1x1200/50

110.0

18500

0.220

0.0151

1232

1208

1790

1535

1x1600/70

120.0

22500

0.230

0.0113

1404

1382

2100

1765

1x2000/95

126.0

26500

0.270

0.0090

1554

1523

2384

1973

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated HV Cables (89/154 kV).