Product Detail

20.3/35 kV or 20.8/36 kV XLPE Insulated, Longitudinally Sealed, Single Core Cables with Copper Conductor

Code

N2XS(F)2Y, CU/XLPE/SCWBT/CWS/WBT/PE

Standards

HD 620 S2, TSEK

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts. In case water sneaks into cable due to any mechanical damage, swellable tape prevents penetration of water inside the cable.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive swelling tape

6. Copper screen

7. Swellable tape

8. PE outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

20.3/35 kV 

 

 

20.8/36kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

37.5

1250

1000

0.524

0.6707

0.690

0.480

0.115

214

192

233

202

1x50/16

38.5

1450

1000

0.387

0.4954

  0.664

0.459

0.125

251

226

279

241

1x70/16

40.5

1700

1000

0.268

0.3430

0.633

0.434

0.140

306

276

348

299

1x95/16

42.0

2000

1000

0.193

0.2470

0.609

   0.416

0.153

363

329

421

362

1x120/16

44.0

   2250

1000

0.153

0.1958

0.590

0.401

0.165

410

373

483

416

1x150/25

45.5

2700

1000

0.124

0.1587

0.572

0.389

0.178

449

415

540

469

1x185/25

47.5

3050

1000

0.0991

0.1268

0.556

0.376

0.191

503

468

614

536

1x240/25

50.0

3650

1000

0.0754

0.0965

0.535

0.363

0.209

576

541

718

630

1x300/25

52.5

4300

1000

0.0601

0.0769

0.519

0.351

0.226

641

608

813

717

1x400/35

55.5

5450

500

0.0470

0.0602

0.497

0.338

0.252

697

684

904

823

1x500/35

    59.0

6500

500

0.0366

0.0468

0.481

0.328

0.274

768

762

1011

929

1x630/35

62.5

7800

500

0.0283

0.0362

0.464

0.317

0.300

 858

847

1128

1043

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, Longitudinally Sealed, Single Core MV Cables (20.3/35 kV).