8.7/15 kV XLPE Insulated, Longitudinally Sealed, Single Core Cables with Copper Conductor
Code N2XS(F)2Y, CU/XLPE/SCWBT/CWS/WBT/PE Standards IEC 60502-2, VDE 0276-620 |
Application Characterized with low
dielectric loss. Used in energy networks where load may change suddenly. Laid
in residential or industrial areas, and underground in ducts. In case water
sneaks into cable due to any mechanical damage, swellable tape prevents
penetration of water inside the cable. Construction 1. Stranded copper conductors 2. Inner
semi-conductive layer 3. XLPE
insulation 4. Outer
semi-conductive layer 5.
Semi-conductive swelling tape 6. Copper
screen 7.
Swellable tape 8. PE outer
jacket |
||||||||||||||
Technical
Data |
|
|
|||||||||||||
Max. operating temperature |
: |
90 oC |
|||||||||||||
Max. short circuit temperature |
: |
250 oC (Max. 5 sec.) |
|||||||||||||
Rated voltage |
: |
8.7/15 kV |
|||||||||||||
Min. bending radius |
: |
15 x D |
|||||||||||||
(D: Cable outer diameter) |
|||||||||||||||
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
||||||||||||||
Nominal |
Overall |
Net |
Delivery Length |
DC
Conductor |
DC
Conductor |
Operation
Inductance |
Operation Capacitance |
Current
Carrying Capacity (A) |
|||||||
Cross |
Diameter |
Weight |
Resistance
at |
Resistance
at |
|||||||||||
Section |
(approx.) |
(approx.) |
20 0C
Max |
90 0C
Max |
|||||||||||
|
|
|
|
|
|
|
|
|
In
ground at 20oC |
In
air at 30oC |
|||||
mm2 |
mm |
kg/km |
m |
Ohm/km |
Ohm/km |
mH/km |
mH/km |
µF/km |
|||||||
|
|
|
|
|
|
*** |
*** |
|
*** |
*** |
*** |
*** |
|||
1x35/16 |
28.0 |
850 |
1000 |
0.524 |
0.6707 |
0.672 |
0.422 |
0.181 |
212 |
187 |
231 |
195 |
|||
1x50/16 |
29.0 |
1000 |
1000 |
0.387 |
0.4954 |
0.646 |
0.403 |
0.201 |
249 |
220 |
277 |
234 |
|||
1x70/16 |
30.5 |
1250 |
1000 |
0.268 |
0.3430 |
0.615 |
0.381 |
0.229 |
303 |
269 |
345 |
292 |
|||
1x95/16 |
32.0 |
1500 |
1000 |
0.193 |
0.2470 |
0.591 |
0.364 |
0.255 |
358 |
321 |
418 |
354 |
|||
1x120/16 |
34.5 |
1750 |
1000 |
0.153 |
0.1958 |
0.572 |
0.353 |
0.278 |
404 |
364 |
481 |
407 |
|||
1x150/25 |
35.5 |
2150 |
1000 |
0.124 |
0.1587 |
0.555 |
0.341 |
0.302 |
441 |
405 |
537 |
460 |
|||
1x185/25 |
37.5 |
2500 |
1000 |
0.0991 |
0.1268 |
0.539 |
0.332 |
0.328 |
493 |
457 |
612 |
527 |
|||
1x240/25 |
40.5 |
3100 |
1000 |
0.0754 |
0.0965 |
0.519 |
0.321 |
0.363 |
563 |
528 |
716 |
621 |
|||
1x300/25 |
42.5 |
3700 |
1000 |
0.0601 |
0.0769 |
0.502 |
0.311 |
0.398 |
626 |
593 |
811 |
709 |
|||
1x400/35 |
46.0 |
4800 |
1000 |
0.0470 |
0.0602 |
0.482 |
0.301 |
0.447 |
676 |
665 |
901 |
815 |
|||
1x500/35 |
49.5 |
5750 |
500 |
0.0366 |
0.0468 |
0.466 |
0.293 |
0.491 |
743 |
739 |
1006 |
921 |
|||
1x630/35 |
53.0 |
7000 |
500 |
0.0283 |
0.0362 |
0.450 |
0.285 |
0.543 |
820 |
818 |
1130 |
1045 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground :
200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load
factor 0.7
In Air :
300C; load factor 1.0
*** :
Flat formation; clearance between cables in air = 1 x cable outer diameter; in
ground = 7cm
*** :
Trefoil formation
Number of System : 1
Resources
Get a copy of brochure on Cu Conductor, XLPE Insulated, Longitudinally Sealed, Single Core MV Cables (8.7/15 kV).