Product Detail

0.6/ 1kV XLPE Insulated, Multi- Core Cables with Copper Conductor

Code

YXV-U, YXV-R, CU/XLPE/PVC, N2XY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603, BS 7889

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, industrial plants, and at places where there is no risk of mechanical damage.

Construction

1. Solid or stranded copper conductors

2. XLPE insulation

3. Filler

4. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

12 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

4x1,5

12.0

200

1000

12.1

30

24

 

4x2,5

13.0

250

1000

7.41

40

32

 

4x4

14.0

350

1000

4.61

52

42

 

4x6

15.5

450

1000

3.08

64

53

 

4x10

17.5

630

1000

1.83

86

73

 

4x16

20.5

905

1000

1.15

111

96

 

4x25

24.5

1400

1000

0.727

143

130

 

4x35

27.0

1850

1000

0.524

173

160

 

4x50

30.5

2500

1000

0.387

205

195

 

4x70

35.5

3500

1000

0.268

252

247

 

4x95

39.5

4650

1000

0.193

303

305

 

4x120

44.5

5900

500

0.153

346

355

 

4x150

49.0

7200

500

0.124

390

407

 

4x185

54.5

8950

500

0.0991

441

469

 

4x240

62.0

11600

250

0.0754

511

551

 

4x300

70.0

14400

250

0.0601

580

638

 

4x400

80.0

19000

250

0.0470

663

746

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, Multi Core (4) LV Cables.