Product Detail

20.3/35 kV or 20.8/36 kV XLPE Insulated, Round Aluminum Wire Armored Single Core Cables with Copper Conductor

Code

N2XSYR(A)Y, CU/XLPE/CWS/PVC/AWA/PVC

Standards

HD 620 S2, TSEK

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Polyester tape

8. Inner sheath

9. Round aluminum wire

10. Polyester tape

11. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

20.3/35 kV

 

 

20.8/36 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

42.0

2070

1000

0.524

0.6707

  0.657

0.367

0.115

214

192

233

202

1x50/16

44.1

2265

1000

0.387

0.4954

   0.632

0.351

0.125

251

226

279

241

1x70/16

45.8

2550

1000

0.268

0.3430

  0.601

  0.332

     0.140

306

276

348

299

1x95/16

48.2

3080

1000

0.193

0.2470

  0.577

  0.318

0.153

363

329

421

362

1x120/16

50.5

    3420

1000

0.153

0.1958

  0.558

  0.308

0.165

410

373

483

416

1x150/25

52.1

3830

1000

0.124

0.1587

  0.541

0.299

0.178

449

415

540

469

1x185/25

54.2

4325

1000

 0.0991

0.1268

  0.525

 0.292

      0.191

503

468

614

536

1x240/25

56.6

5025

1000

 0.0754

0.0965

  0.506

0.284

0.209

576

541

718

630

1x300/25

58.5

    5670

500

 0.0601

0.0769

  0.490

0.279

0.226

641

608

813

717

1x400/35

62.3

6850

500

 0.0470

0.0602

  0.471

0.275

0.252

697

684

904

823

1x500/35

     65.8

8065

500

 0.0366

0.0468

  0.456

0.270

0.274

768

762

1011

929

1x630/35

 68.0

9565

500

 0.0283

0.0362

0.440

  0.264

0.300

  858

847

1128

1043

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1