Product Detail
3.6/6 kV XLPE Insulated, Round Aluminum Wire Armored Single Core Cables with Copper Conductor
Code N2XSYR(A)Y, CU/XLPE/CWS/PVC/AWA/PVC Standards IEC 60502-2, VDE 276-620, BS 6622 Technical
Data |
Application Characterized with low
dielectric loss. Used in energy networks where load may change suddenly. Laid
in residential or industrial areas, and underground in ducts. Construction 1. Stranded copper conductors 2. Inner
semi-conductive layer 3. XLPE
insulation 4. Outer
semi-conductive layer 5.
Semi-conductive tape 6. Copper
screen 7.
Polyester tape 8. Inner
sheath 9. Round
aluminum wire 10.
Polyester tape 11. PVC
outer jacket |
||||||||||||||
Max. operating temperature |
: |
90 oC |
|||||||||||||
Max. short circuit temperature |
: |
250 oC (Max. 5 sec.) |
|||||||||||||
Rated voltage |
: |
3.6/6 kV |
|||||||||||||
Min. bending radius |
: |
15 x D |
|||||||||||||
(D: Cable outer diameter) |
|||||||||||||||
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
||||||||||||||
Nominal |
Overall |
Net |
Delivery Length |
DC
Conductor |
DC
Conductor |
Operation
Inductance |
Operation Capacitance |
Current
Carrying Capacity (A) |
|||||||
Cross |
Diameter |
Weight |
Resistance
at |
Resistance
at |
|||||||||||
Section |
(approx.) |
(approx.) |
20 0C
Max |
90 0C
Max |
|||||||||||
|
|
|
|
|
|
|
|
|
In
ground at 20oC |
In
air at 30oC |
|||||
mm2 |
mm |
kg/km |
m |
Ohm/km |
Ohm/km |
mH/km |
mH/km |
µF/km |
|||||||
|
|
|
|
|
|
*** |
*** |
|
*** |
*** |
*** |
*** |
|||
1x35/16 |
26.2 |
1135 |
1000 |
0.524 |
0.6707 |
0.657 |
0.367 |
0.283 |
201 |
191 |
238 |
199 |
|||
1x50/16 |
27.3 |
1280 |
1000 |
0.387 |
0.4954 |
0.632 |
0.351 |
0.318 |
241 |
227 |
285 |
241 |
|||
1x70/16 |
29.0 |
1530 |
1000 |
0.268 |
0.3430 |
0.601 |
0.332 |
0.368 |
301 |
277 |
356 |
301 |
|||
1x95/16 |
31.0 |
1840 |
1000 |
0.193 |
0.2470 |
0.577 |
0.318 |
0.414 |
364 |
331 |
435 |
365 |
|||
1x120/16 |
32.3 |
2110 |
1000 |
0.153 |
0.1958 |
0.558 |
0.308 |
0.455 |
424 |
379 |
496 |
419 |
|||
1x150/25 |
34.7 |
2600 |
1000 |
0.124 |
0.1587 |
0.541 |
0.299 |
0.499 |
479 |
422 |
554 |
479 |
|||
1x185/25 |
36.6 |
3000 |
1000 |
0.0991 |
0.1268 |
0.525 |
0.292 |
0.544 |
549 |
476 |
637 |
543 |
|||
1x240/25 |
39.4 |
3640 |
1000 |
0.0754 |
0.0965 |
0.506 |
0.284 |
0.587 |
640 |
550 |
746 |
640 |
|||
1x300/25 |
41.8 |
4270 |
1000 |
0.0601 |
0.0769 |
0.490 |
0.279 |
0.603 |
724 |
619 |
846 |
731 |
|||
1x400/35 |
46.9 |
5535 |
500 |
0.0470 |
0.0602 |
0.471 |
0.275 |
0.642 |
795 |
695 |
941 |
840 |
|||
1x500/35 |
50.6 |
6670 |
500 |
0.0366 |
0.0468 |
0.456 |
0.270 |
0.667 |
883 |
773 |
1051 |
949 |
|||
1x630/35 |
54.5 |
8130 |
500 |
0.0283 |
0.0362 |
0.440 |
0.264 |
0.739 |
981 |
856 |
1180 |
1076 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground :
200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load
factor 0.7
In Air :
300C; load factor 1.0
*** :
Flat formation; clearance between cables in air = 1 x cable outer diameter; in
ground = 7cm
*** :
Trefoil formation
Number of System : 1
Resources
Get a copy of brochure on Cu Conductor, XLPE Insulated, RAW Armored, Single Core MV Cables (3.6/6 kV).