3.6/6 kV XLPE Insulated, Radial and Longitudinally Sealed, Single Core Cables with Copper Conductor

Code

N2XS(FL)2Y, CU/XLPE/LW/CWS/LW/PE

Standards

IEC 60502-2, VDE 0276-620

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts. In case water sneaks into cable due to any mechanical damage, swellable tape prevents penetration of water inside the cable.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive swelling tape

6. Copper screen

7. Swellable tape

8. PE coated aluminum foil

9. PE outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

3.6/6 kV  

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

25.0

800

1000

0.524

0.6707

0.665

0.395

0.283

201

191

238

199

1x50/16

26.0

900

1000

0.387

0.4954

0.640

0.381

0.318

241

227

285

241

1x70/16

27.5

1150

1000

0.268

0.3430

0.609

0.361

0.368

301

277

356

301

1x95/16

29.5

1400

1000

0.193

0.2470

0.585

0.345

0.414

364

331

435

365

1x120/16

31.0

1600

1000

0.153

0.1958

0.566

0.333

0.455

424

379

496

419

1x150/25

32.5

2050

1000

0.124

0.1587

0.549

0.323

0.499

479

422

554

479

1x185/25

34.5

2400

1000

0.0991

0.1268

0.533

0.315

0.544

549

476

637

543

1x240/25

37.5

2950

1000

0.0754

0.0965

0.513

0.306

0.587

640

550

746

640

1x300/25

40.0

3600

1000

0.0601

0.0769

0.498

0.300

0.603

724

619

846

731

1x400/35

44.0

4700

1000

0.0470

0.0602

0.478

0.292

0.642

795

695

941

840

1x500/35

47.5

5700

500

0.0366

0.0468

0.463

0.286

0.667

883

773

1051

949

1x630/35

51.5

6950

500

0.0283

0.0362

0.947

0.278

0.739

891

856

1180

1076

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, R&L Armored, Single Core MV Cables (3.6/6 kV).