8.7/15 kV XLPE Insulated, Round Steel Wire Armored, Three Core Cables with Copper Conductor

Code

YXC8VZ2V-R, N2XSEYRY, CU/XLPE/CTS/PVC/SWA/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502 - 2, VDE 0276 – 620, BS 6622

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Filler

8. Inner sheath

9. Galvanized round steel wire

10. Polyester tape

11. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

8.7/15 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

60.5

5750

500

0.524

0.397

0.160

178

173

3x50/16

64.0

7500

500

0.387

0.377

0.175

210

206

3x70/16

68.0

8800

500

0.268

0.356

0.196

256

257

3x95/16

72.0

10200

500

0.193

0.339

0.218

307

313

3x120/16

76.0

10200

250

0.153

0.325

0.240

349

360

3x150/25

81.0

12750

250

0.124

0.315

0.258

392

410

3x185/25

85.0

14500

250

0.0991

0.305

0.280

443

469

3x240/25

92.0

17150

250

0.0754

0.292

0.315

513

553

3x300/25

97.0

19750

250

0.0601

0.284

0.343

576

635

3x400/35

105.0

24000

200

0.0470

0.273

0.385

650

731

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, RSW Armored, 3-Core MV Cables (8.7/15 kV).