Product Detail

0.6/ 1kV XLPE Insulated, Round Steel Wire Armored Control Cables with Copper Conductor

Code

YXZ2V-U, YXZ2V-R, CU/XLPE/SWA/PVC, N2XRY

U: Solid conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, BS 5467

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Solid or stranded copper conductors

2. XLPE insulation

3. Filler

4. Galvanized round steel wire

5. Polyester tape

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

mm2

mm

kg/km

m

Ohm/km

A

A

5x1,5

15.0

420

1000

12.1

21.0

18.0

6x1,5

16.5

470

1000

12.1

19.5

16.8

7x1,5

16.5

480

1000

12.1

18.0

15.6

8x1,5

18.0

670

1000

12.1

16.5

14.4

10x1,5

19.5

800

1000

12.1

15.0

13.2

12x1,5

20.0

850

1000

12.1

14.3

12.6

14x1,5

20.5

900

1000

12.1

13.5

12.0

16x1,5

21.5

950

1000

12.1

12.8

11.4

19x1,5

22.0

1050

1000

12.1

12.0

10.8

21x1,5

24.0

1300

1000

12.1

11.3

10.2

24x1,5

25.5

1450

1000

12.1

10.5

9.6

27x1,5

26.0

1500

1000

12.1

10.2

9.4

30x1,5

27.0

1600

1000

12.1

9.9

9.1

37x1,5

28.5

1800

1000

12.1

9.3

8.6

40x1,5

29.5

1950

1000

12.1

9.0

8.4

48x1,5

32.0

2250

1000

12.1

8.4

7.9

52x1,5

32.5

2350

1000

12.1

7.8

7.4

61x1,5

35.5

2900

1000

12.1

7.5

7.2

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, RSW Armored Control Cables (1).