Product Detail

0.6/ 1kV XLPE Insulated, Round Steel Wire Armored, Multi-Core Cables with Copper Conductor

Code

YXZ2V-U, YXZ2V-R, CU/XLPE/SWA/PVC, N2XRY

U: Solid conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, BS 5467

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts; in power or switching stations; at local energy distribution networks; industrial plants where risk of mechanical damage exits.

Construction

1. Solid or stranded copper conductors

2. XLPE insulation

3. Filler

4. Galvanized round steel wire

5. Polyester tape

6. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

3x1,5

14.5

395

1000

12.1

30

24

 

3x2,5

15.5

460

1000

7.41

40

32

 

3x4

16.5

540

1000

4.61

52

42

 

3x6

17.8

640

1000

3.08

64

53

 

3x10

20.0

950

1000

1.83

86

73

 

3x16

22.0

1200

1000

1.15

111

96

 

3x25

26.0

1800

1000

0.727

143

130

 

3x35

28.0

2200

1000

0.524

173

160

 

3x50

31.0

2800

1000

0.387

205

195

 

3x70

36.5

4000

1000

0.268

252

247

 

3x95

40.5

5000

500

0.193

303

305

 

3x120

44.5

6050

500

0.124

346

355

 

3x150

50.0

7750

500

0.153

390

407

 

3x185

55.0

9300

500

0.0991

441

469

 

3x240

61.5

11650

250

0.0754

511

551

 

3x300

69.0

14000

250

0.0601

580

638

 

3x400

77.0

18000

250

0.0470

663

746

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, RSW Armored, Multi Core (3) LV Cables.