Product Detail
0.6/ 1kV XLPE Insulated, Round Steel Wire Armored, Multi-Core Cables with Copper Conductor
Code YXZ2V-U, YXZ2V-R, CU/XLPE/SWA/PVC, N2XRY U: Solid conductor R: Stranded Rigid Conductor Standards IEC 60502-1, BS 5467 |
Application Characterized with low dielectric
loss. Used indoor, outdoor or underground; in cable ducts; in power or
switching stations; at local energy distribution networks; industrial plants
where risk of mechanical damage exits. Construction 1. Stranded
copper conductors 2. XLPE
insulation 3. Filler 4. Galvanized
round steel wire 5.
Polyester tape 6. PVC
outer jacket |
|||||||||
Technical
Data |
|
|
||||||||
Max. operating temperature |
: |
90 oC |
||||||||
Max. short circuit
temperature |
: |
250 oC (Max. 5
sec.) |
||||||||
Rated voltage |
: |
0.6 / 1kV |
||||||||
Min. bending radius |
: |
15 x D |
||||||||
(D: Cable outer diameter) |
||||||||||
DIMENSIONS
AND WEIGHTS |
ELECTRICAL
PROPERTIES |
|
||||||||
Nominal |
Overall |
|
|
DC
Conductor |
Current
Carrying Capacity |
|
||||
Cross- |
Diameter |
Net
Weight |
Delivery |
Resistance
at |
In
Ground at |
In Air
at |
|
|||
Section |
(approx.) |
(approx.) |
Length |
200C
Max |
200C |
300C |
|
|||
mm2 |
mm |
kg/km |
m |
Ohm/km |
A |
A |
|
|||
4x1,5 |
15.3 |
430 |
1000 |
12.1 |
30 |
24 |
|
|||
4x2,5 |
16.4 |
510 |
1000 |
7.41 |
40 |
32 |
|
|||
4x4 |
17.6 |
615 |
1000 |
4.61 |
52 |
42 |
|
|||
4x6 |
20.0 |
800 |
1000 |
3.08 |
64 |
53 |
|
|||
4x10 |
21.0 |
1100 |
1000 |
1.83 |
86 |
73 |
|
|||
4x16 |
24.0 |
1550 |
1000 |
1.15 |
111 |
96 |
|
|||
4x25 |
28.0 |
2150 |
1000 |
0.727 |
143 |
130 |
|
|||
4x35 |
30.5 |
2700 |
1000 |
0.524 |
173 |
160 |
|
|||
4x50 |
34.0 |
3400 |
1000 |
0.387 |
205 |
195 |
|
|||
4x70 |
40.0 |
4850 |
1000 |
0.268 |
252 |
247 |
|
|||
4x95 |
44.0 |
6150 |
1000 |
0.193 |
303 |
305 |
|
|||
4x120 |
50.5 |
8000 |
500 |
0.124 |
346 |
355 |
|
|||
4x150 |
55.0 |
9600 |
500 |
0.153 |
390 |
407 |
|
|||
4x185 |
60.5 |
11570 |
250 |
0.0991 |
441 |
469 |
|
|||
4x240 |
68.0 |
14550 |
250 |
0.0754 |
511 |
551 |
|
|||
4x300 |
76.0 |
17750 |
250 |
0.0601 |
580 |
638 |
|
|||
4x400 |
87.0 |
23800 |
250 |
0.0470 |
663 |
746 |
|
|||
NOTE : Current carrying
capacities are valid under the following conditions.
In ground : 200C; buried in 70
cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7
In Air : 300C; load
factor 1.0
Number of System : 1
Resources
Get a copy of brochure on Cu Conductor, XLPE Insulated, RSW Armored, Multi Core (4) LV Cables.