Product Detail

0.6/ 1kV XLPE Insulated, Single Core Cables with Copper Conductor

Code

YXV-U, YXV-R, CU/XLPE/PVC, N2XY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603, BS 7889

Application

Characterized with low dielectric loss. Used indoor, outdoor or underground; in cable ducts, at power or switching stations, local energy distribution networks, industrial plants, and at places where there is no risk of mechanical damage.

Construction

1. Solid or stranded copper conductors

2. XLP insulation

3. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature   

:

250 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity (A)

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

***

***

***

***

 

1x1,5

5.5

45

1000

12.1

39

32

32

25

 

1x2,5

6.0

55

1000

7.41

51

43

42

34

 

1x4

6.5

75

1000

4.61

66

55

56

44

 

1x6

7.0

90

1000

3.08

82

68

71

57

 

1x10

8.0

140

1000

1.83

109

90

96

77

 

1x16

9.0

200

1000

1.15

139

115

128

102

 

1x25

10.5

300

1000

0.727

179

149

173

139

 

1x35

11.5

400

1000

0.524

213

178

212

170

 

1x50

13.0

530

1000

0.387

251

211

258

208

 

1x70

15.0

750

1000

0.268

307

259

328

265

 

1x95

17.0

1000

1000

0.193

366

310

404

326

 

1x120

18.5

1250

1000

0.153

416

352

471

381

 

1x150

20.5

1550

1000

0.124

465

396

541

438

 

1x185

22.5

1900

1000

0.0991

526

449

626

507

 

1x240

25.5

2450

1000

0.0754

610

521

749

606

 

1x300

29.0

3000

1000

0.0601

689

587

864

697

 

1x400

32.0

4000

1000

0.0470

788

669

1018

816

 

1x500

35.5

5000

1000

0.0366

889

748

1173

933

 

1x630

39.0

6100

1000

0.0283

980

843

1315

1083

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources