Product Detail

12/20 kV or 12.7/22 kV XLPE Insulated, Single Core Cables with Copper Conductor

Code

YXC7V-R, N2XSY, CU/XLPE/CWS/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502-2, VDE 0276-620

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Polyester tape

8. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

12 /20 kV

 

 

12.7/ 22 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

27.0

950

1000

0.524

0.6707

0.670

0.416

0.157

213

189

233

199

1x50/16

28.5

1150

1000

0.387

0.4954

0.644

0.397

0.174

250

223

279

238

1x70/16

30.0

1400

1000

0.268

0.3430

0.614

0.377

0.197

304

273

347

296

1x95/16

32.0

1650

1000

0.193

0.2470

0.590

  0.360

0.218

361

325

420

358

1x120/16

34.0

1950

1000

0.153

0.1958

0.571

0.349

0.238

407

368

483

412

1x150/25

35.0

2350

1000

0.124

0.1587

0.554

0.338

0.258

445

410

540

466

1x185/25

37.0

2700

1000

0.0991

0.1268

0.538

0.329

0.278

498

463

614

534

1x240/25

39.5

3300

1000

0.0754

0.0965

0.518

0.317

0.308

569

534

718

627

1x300/25

42.0

3900

1000

0.0601

0.0769

0.501

0.308

0.336

633

601

813

715

1x400/35

45.5

5000

1000

0.0470

0.0602

0.480

0.298

0.377

686

674

904

819

1x500/35

48.5

6000

500

0.0366

0.0468

0.464

0.290

0.413

756

750

1011

927

1x630/35

52.5

7300

500

0.0283

0.0362

0.448

0.282

0.455

843

836

1128

1041

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, Single Core MV Cables (12/20 kV).