Product Detail

5.8/10 kV (6/10 kV) or 6.35/11 kV XLPE Insulated, Single Core Cables with Copper Conductor

Code

YXC7V-R, N2XSY, CU/XLPE/CWS/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502-2, VDE 0276-620

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Polyester tape

8. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

5.8 /10 kV (6/10 kV)

 

 

6.35/11 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Overall

Net

Delivery

Length

DC Conductor

DC Conductor

Operation Inductance

Operation

Capacitance

Current Carrying Capacity

(A)

Cross

Diameter

Weight

Resistance at

Resistance at

Section

(approx.)

(approx.)

20 0C Max

90 0C Max

 

 

 

 

 

 

 

 

 

In ground

at 20oC

In air

at 30oC

mm2

mm

kg/km

m

Ohm/km

Ohm/km

mH/km

mH/km

µF/km

 

 

 

 

 

 

***

***

 

***

***

***

***

1x35/16

22.5

800

1000

0.524

0.6707

0.661

0.383

0.223

212

187

231

195

1x50/16

24.0

950

1000

0.387

0.4954

0.636

0.366

0.248

249

220

277

234

1x70/16

26.0

1200

1000

0.268

0.3430

0.606

0.349

0.285

303

269

345

292

1x95/16

27.5

1450

1000

0.193

0.2470

0.582

0334

0.320

358

321

418

354

1x120/16

29.5

1700

1000

0.153

0.1958

0.563

0.323

0.350

404

364

481

407

1x150/25

30.5

2100

1000

0.124

0.1587

0.546

0.313

0.382

441

405

537

460

1x185/25

32.5

2450

1000

0.0991

0.1268

0.529

0.301

0.415

493

457

612

527

1x240/25

35.0

3050

1000

0.0754

0.0965

0.509

0.294

0.462

563

528

716

621

1x300/35

37.5

3650

1000

0.0601

0.0769

0.493

0.288

0.507

626

593

811

709

1x400/35

410

4700

1000

0.0470

0.0602

0.473

0.278

0.573

676

665

901

815

1x500/35

44.0

5700

500

0.0366

0.0468

0.457

0.271

0.631

743

739

1006

921

1x630/35

47.5

7000

500

0.0283

0.0362

0.440

0.264

0.699

820

818

1130

1045

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, Single Core MV Cables (5.8/10 kV).